10-15-20 kVA
Three Phase / Three Phase
Three Level Inverter
Digital Power Factor Correction
Technical Specifications |
|||
INPUT | |||
Power (kVA) | 10 | 15 | 20 |
Voltage | 380 / 400 / 415 Vac 3ph + N | ||
Voltage Tolerances | - 25%, +20% (without downgrading) | ||
Frequency | 50 / 60 Hz | ||
Frequency Tolerances | ± 10% | ||
Power Factor | ? 0,99 | ||
THDi | < 5% | ||
OUTPUT | |||
Voltage | 380 / 400 / 415 Vac 3ph + N | ||
Voltage Tolerances | ± 1% (static load), dynamic load in accordance with VFI-SS-11 | ||
Frequency | 50 / 60 Hz | ||
Frequency Tolerances | ± 0.1% (self-synchronize), ± 1% (mains-synchronize) | ||
Power Factor | 0,8 | ||
THDv | ? 2% (linear load), ? 5% (non-linear load) | ||
Crest Factor | 3:1 | ||
GENERAL | |||
Technology | Three level inverter, PFC | ||
Control | Dual-DSP, SPWM | ||
Paralleling Units | Up to 6 units | ||
Communication | SNMP(Optional), RS232, RS485, MODEM, MODBUS | ||
Remote Monitoring | SNMPView, Remote monitoring panel(optional) | ||
Dry Contacts | Programmable 3 dry contacts | ||
Custom Inputs | Generator, Remote EPO, Remote Start/Stop | ||
Cold Start | Standard | ||
Maintenance Bypass | Standard |